Modbus TCP vs. Modbus RTU: MBAP Header, Function Codes & Exception Diagnostics

In-depth comparison of Modbus RTU (RS-485 serial) and Modbus TCP (Ethernet port 502), detailing the 7-byte MBAP header, Protocol Data Unit (PDU), function codes 01–16, zero-based vs. one-based addressing, and exception codes.
Interactive Workstation Available: Test the protocols and algorithms covered in this guide live in your browser using TCP/UDP & Serial Port Tester.
Launch TCP/UDP & Serial Port Tester ➔

Originally published by Modicon in 1979 for programmable logic controllers, Modbus remains the most universally supported open communication protocol in industrial automation, smart grid power meters, VFD motor drives, temperature controllers, and building management systems. While the core Protocol Data Unit (PDU)—consisting of a 1-byte Function Code and variable Data payload—is identical across variants, the framing and error-detection layers differ fundamentally between serial Modbus RTU and Ethernet Modbus TCP.

1. Structural Comparison: ADU Framing

An complete Modbus packet on the wire is called an Application Data Unit (ADU). Understanding how the ADU wraps the core PDU is critical when debugging protocol converters (e.g., Moxa MGate or RS-485-to-Ethernet gateways):

  • Modbus RTU ADU (Serial RS-485 / RS-232): [1-Byte Slave ID] + [PDU: Function Code + Data] + [2-Byte CRC-16 (LE)]. Frames are delimited on the physical serial bus by a silent idle interval of at least 3.5 character times ($t_{3.5}$).
  • Modbus TCP ADU (Ethernet Port 502): [7-Byte MBAP Header] + [PDU: Function Code + Data]. Because TCP already guarantees reliable delivery with hardware Ethernet FCS and TCP checksums, the 2-byte CRC-16 tail is removed and replaced by a 7-byte Modbus Application Protocol (MBAP) Header at the front of the packet.
MBAP Header Field Byte Length Byte Order Description & Gateway Behavior
Transaction Identifier 2 Bytes Big-Endian Incrementing sequence number generated by the client and echoed by the server to pair concurrent TCP requests.
Protocol Identifier 2 Bytes Big-Endian Always 00 00 for standard Modbus TCP.
Length Field 2 Bytes Big-Endian Byte count of all following bytes, including the 1-byte Unit Identifier plus the entire PDU.
Unit Identifier (Slave ID) 1 Byte Single Byte 0x01–0xF7 when routing through a Modbus TCP-to-RTU serial bridge; 0x00 or 0xFF for standalone TCP servers.

2. Standard Function Codes & Register Memory Tables

Modbus organizes device memory into four conceptual tables. Unlike MELSEC PLCs (which use Little-Endian), all 16-bit addresses and register values inside a Modbus PDU are transmitted in Big-Endian (Most Significant Byte first) network order:

Function Code Hex Target Memory Table Traditional 5-Digit Reference Access Type & Max Count per Frame
Read Coils 0x01 Discrete Output Coils 00001 – 09999 Read-Write (1-Bit). Up to 2,000 coils per request.
Read Discrete Inputs 0x02 Discrete Input Contacts 10001 – 19999 Read-Only (1-Bit). Up to 2,000 inputs per request.
Read Holding Registers 0x03 16-Bit Output/Config Registers 40001 – 49999 Read-Write (16-Bit). Up to 125 registers (250 bytes) per request.
Read Input Registers 0x04 16-Bit Analog/Sensor Inputs 30001 – 39999 Read-Only (16-Bit). Up to 125 registers per request.
Write Single Coil 0x05 Discrete Output Coils 00001 – 09999 Write-Only. Value FF 00 = ON (1), 00 00 = OFF (0).
Write Single Register 0x06 16-Bit Holding Registers 40001 – 49999 Write-Only. Echoes the exact request frame upon success.
Write Multiple Coils 0x0F (15) Discrete Output Coils 00001 – 09999 Write-Only. Packs multiple bit states into byte-aligned payload.
Write Multiple Registers 0x10 (16) 16-Bit Holding Registers 40001 – 49999 Write-Only. Up to 123 contiguous 16-bit registers per request.

3. The "Off-by-One" Addressing Trap (40001 vs. Offset 0x0000)

One of the most frequent sources of commissioning errors is the discrepancy between 1-based documentation notation and 0-based wire protocol addressing:

  • In vendor manuals, Holding Register #1 is written as 40001 (or 400001 in 6-digit notation), where the leading digit 4 merely denotes the "Holding Register" table.
  • On the wire, the Function Code (0x03) already specifies the Holding Register table, and the 2-byte starting address field is 0-indexed. Therefore, to read Holding Register 40001, the wire packet sends starting address 0x0000. To read 40101, the wire packet sends 0x0064 (decimal 100).

4. Packet Dissection & Exception Response Decoding

# Read 2 Holding Registers (40001..40002) from Slave 1
# 1) Modbus RTU Request (8 Bytes):
01 03 00 00 00 02 C4 0B
# [01: Slave 1] [03: Func] [00 00: Start Addr 0] [00 02: Qty 2] [C4 0B: CRC-16 LE]

# 2) Equivalent Modbus TCP Request (12 Bytes):
00 01 00 00 00 06 01 03 00 00 00 02
# [00 01: TxID] [00 00: Proto] [00 06: Len] [01: UnitID] [03 00 00 00 02: PDU]

When a slave rejects a command, it sets the Most Significant Bit of the Function Code (`Func | 0x80`, so `0x03` becomes `0x83`) and returns a 1-byte Exception Code:

  • 0x01 (Illegal Function): The slave does not implement the requested function code (e.g., sending 0x06 to a device that only supports 0x10).
  • 0x02 (Illegal Data Address): The starting address or `Start + Quantity` falls outside the device's valid register map.
  • 0x03 (Illegal Data Value): A payload parameter is malformed (e.g., sending 0x0001 instead of 0xFF00 for Function 0x05 Write Single Coil).
  • 0x04 (Slave Device Failure): An unrecoverable internal hardware error occurred while attempting the action.

Frequently Asked Questions (FAQ)

Q. Why does Modbus TCP not include a 2-byte CRC-16 checksum at the end of the packet?

Modbus TCP runs over TCP/IP and Ethernet, which already enforce 32-bit Ethernet Frame Check Sequences (FCS) and 16-bit TCP segment checksums. Adding an application-layer CRC-16 would be redundant.

Q. Why does my response value appear shifted by one register compared to the device manual?

Some vendor manuals list 1-based register numbers (40001 = address 1) while the Modbus wire protocol uses 0-based offsets (40001 = wire address 0x0000). Subtract 1 from the manual's register number if values are shifted.

Q. What does a Modbus response starting with Function Code 0x83 and byte 0x02 mean?

0x83 is 0x03 + 0x80, indicating an Exception Response to Read Holding Registers. Exception code 0x02 means Illegal Data Address—one or more requested register addresses do not exist on the slave.

Q. How are 32-bit floating-point values transmitted over 16-bit Modbus registers?

A 32-bit IEEE 754 float spans two consecutive 16-bit registers. Depending on the vendor, word order may be Big-Endian (ABCD) or Mid-Little-Endian Word-Swapped (CDAB).